Skip to main content

Over 150 LLM Providers · Over 5,300 Models The most extensible AI-powered pentesting platform. Open source. Star on GitHub

CVE-2017-14469

10.0 · CRITICAL
Published Apr 5, 2018 rockwellautomation

Overview

CVE-2017-14469 is a critical-severity vulnerability affecting rockwellautomation micrologix_1400_b_firmware. It was published on April 5, 2018 and has a CVSS 3.0 base score of 10.0 (CRITICAL).

This vulnerability has a CVSS 3.0 base score of 10.0, rated CRITICAL. It can be exploited remotely over the network. No authentication or special privileges are required for exploitation.

Technical Description

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0028 Fault Type: Non-User Description: Values 0x01 and 0x02 are invalid values for the user fault routine. By writing directly to the file it is possible to set these values. When this is done and the device is moved into a run state, a fault is triggered. NOTE: This is not possible through RSLogix.

Remediation

Check the references section for vendor advisories and patches from rockwellautomation. Update micrologix_1400_b_firmware to the latest patched version. If immediate patching is not possible, review the CVSS vector to understand the attack surface and apply compensating controls such as network segmentation or access restrictions.

Affected Products

Vendor Product Versions Status
rockwellautomation micrologix_1400_b_firmware 0 Affected

Frequently Asked Questions

What is CVE-2017-14469?

CVE-2017-14469 is a critical-severity vulnerability affecting rockwellautomation micrologix_1400_b_firmware. It was published on April 5, 2018 and has a CVSS 3.0 base score of 10.0 (CRITICAL).

How severe is CVE-2017-14469?

This vulnerability has a CVSS 3.0 base score of 10.0, rated CRITICAL. It can be exploited remotely over the network. No authentication or special privileges are required for exploitation.

How do I fix or remediate CVE-2017-14469?

Check the references section for vendor advisories and patches from rockwellautomation. Update micrologix_1400_b_firmware to the latest patched version. If immediate patching is not possible, review the CVSS vector to understand the attack surface and apply compensating controls such as network segmentation or access restrictions.

How can CyberStrike help with CVE-2017-14469?

CyberStrike's AI-powered security agents can automatically detect CVE-2017-14469 across your infrastructure using autonomous pentesting, DAST scanning, and HackBrowser. The platform continuously monitors for known vulnerabilities and provides actionable remediation guidance prioritized by real-world exploitability.