CVE-2022-30319

8.1 · HIGH
Published Jul 28, 2022 honeywell CWE-290 EPSS 0.70% (51th pctl)

Overview

CVE-2022-30319 is a high-severity vulnerability affecting honeywell saia_pg5_controls_suite. It was published on July 28, 2022 and has a CVSS 3.1 base score of 8.1 (HIGH).

This vulnerability has a CVSS 3.1 base score of 8.1, rated HIGH. It requires local or adjacent network access to exploit. No authentication or special privileges are required for exploitation.

Technical Description

Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downl

Remediation

Check the references section for vendor advisories and patches from honeywell. Update saia_pg5_controls_suite to the latest patched version. If immediate patching is not possible, review the CVSS vector to understand the attack surface and apply compensating controls such as network segmentation or access restrictions.

Affected Products

Vendor Product Versions Status

Frequently Asked Questions

What is CVE-2022-30319?

CVE-2022-30319 is a high-severity vulnerability affecting honeywell saia_pg5_controls_suite. It was published on July 28, 2022 and has a CVSS 3.1 base score of 8.1 (HIGH).

How severe is CVE-2022-30319?

This vulnerability has a CVSS 3.1 base score of 8.1, rated HIGH. It requires local or adjacent network access to exploit. No authentication or special privileges are required for exploitation.

How do I fix or remediate CVE-2022-30319?

Check the references section for vendor advisories and patches from honeywell. Update saia_pg5_controls_suite to the latest patched version. If immediate patching is not possible, review the CVSS vector to understand the attack surface and apply compensating controls such as network segmentation or access restrictions.

How can CyberStrike help with CVE-2022-30319?

CyberStrike's AI-powered security agents can automatically detect CVE-2022-30319 across your infrastructure using autonomous pentesting, DAST scanning, and HackBrowser. The platform continuously monitors for known vulnerabilities and provides actionable remediation guidance prioritized by real-world exploitability.